|
Automatic
Blowdown Controllers (ABCO)
ABCO
datasheet
Single/Dual
boiler control
Condensate
Recovery Pump System (CRPS)
Pressure
Reducing Station (PRS)
Flash
Separators (FS)
De-aerator
Heads (DH)
Other
Products
|
Data
Sheet: The need for Automatic Boiler Controller Copyright
Steamline ®, 1st July 1999
Boiler
feed water contains dissolved solids, both from raw water and
water treatment chemicals. While a water softening plant reduces
the “hardness” (i.e. the presence of scale forming
salts), it does not reduce the TDS of the feed water. As steam is
raised from a boiler, the level of concentration of Total
Dissolved Solids (TDS) in the boiler water increases. If
uncontrolled, the TDS level rises above the set point for a
particular boiler, leading to the following problems:
Foaming
& Carryover Pure
water
does not foam when it boils. However, as the amount of impurities
rise, a foam
layer is
formed at the steam separation surface. The amount of foaming is
directly proportional to the TDS level in the boiler. Foaming (or
“priming”) causes carryover of water, or wet
contaminated steam, which may be carried over into the steam
system. The products of carryover would be deposited on heat
transfer surfaces and ancillary equipment, reducing steam system
efficiency and plant productivity. This is what causes fouling of
heat exchangers, malfunctioning of control valves and steam traps
etc.
Scale
Deposition If
the TDS is too high, scale will deposit on the boiler tubes and
furnace (water side). This has the effect of reducing heat
transfer with its subsequent effect on fuel consumption and safe
operation of the boiler.
A
scale deposit 1mm thick on the water side could increase fuel
consumption by 5 to 8% (Source:
PCRA Handbook No. 3 - Efficient Generation of Steam) Tube
surfaces underneath the scale may become overheated leading to
tube damage or tube failure. Figure 1 shows the effect of varying
thickness of common scales on tube temperature.
In order to
prevent these problems, the TDS needs to be controlled within a
certain specified maximum limit. The chart below shows the
recommended water characteristics for shell boilers in accordance
with IS: 10392-1982 and BS: 2486-1964, for pressures up to 25 bar
g:

Blowdown
of the boiler can keep TDS within the required limits. Blowdown is
achieved either by manual or automatic methods. In the manual
method, blowdown is achieved by opening a large bore valve at the
bottom of the drum (or on the side of the drum in case of
continuous blowdown). However, this practice can be highly
wasteful. As the period of blowdown is not related with either
boiler steam load or feedwater purity, the TDS level in manual
methods can vary greatly, causing an average TDS level much lower
than the allowable limit, and leading to excess blowdown.
On
the other hand, an automatic blowdown control system, based on TDS
measurement and subsequent corrective action, can maintain a TDS
level much closer to the set point, resulting in considerable fuel
savings.

As
seen in the graphs above, the automatic control of TDS results in
an average TDS level much closer to the set point. This means that
the actual quantity of blowdown over a period of time gets reduced
compared to the manual method. Blowdown water is water that has
been heated to the saturation temperature of the boiler, so it
contains a lot of heat. At a boiler pressure of 10.5 Kg/cm2
g, each kg of blowdown water contains almost 190 kcal of heat
energy. If an automatic boiler controller can reduce the blowdown
of a 10 TPH boiler from 6% to 3%, i.e. a saving of 3%, the
blowdown quantity would reduce by 300 Kg/hr, or 7200 kg/day. This
would mean a saving of 1368000 kcal/day. This would mean a fuel
saving of approximately 180 litres of oil, if the boiler was fired
with furnace oil. The cost benefit of preventing corrosion in the
boiler and the steam system, though it cannot be quantified
exactly, would be in addition.
Back
|